| AAQL | BODY STYLE | |
| ABXD | BUSHING LENGTH | INCHES MINIMUM 0.332 AND INCHES MAXIMUM 0.380 |
| ADAQ | BODY LENGTH | INCHES MAXIMUM 1.500 |
| ADAT | BODY WIDTH | INCHES MAXIMUM 1.250 |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES MINIMUM 0.594 AND INCHES MAXIMUM 0.656 |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | INCHES MINIMUM 0.344 AND INCHES MAXIMUM 0.406 |
| AEFS | NONTURN DEVICE DIAMETER | INCHES NOMINAL 0.250 |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES MAXIMUM 1.780 |
| AKPX | POLE QUANTITY | 2 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | THREADED BUSHING WITH PANEL SEAL 1 |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | FIRST LOCATION AMPERES DC 10.0 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | SECOND LOCATION AMPERES AC 20.0 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | FIRST LOCATION DC 50.0 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | SECOND LOCATION AC 240.0 |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | SECOND LOCATION AC 1000.0 |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | FIRST LOCATION DC 500.0 |
| CPRH | CIRCUIT PROTECTION TYPE | SECOND LOCATION OVERCURRENT |
| CPRH | CIRCUIT PROTECTION TYPE | FIRST LOCATION OVERVOLTAGE |
| CPRJ | TRIP RELEASE METHOD | ALL LOCATIONS MAGNETIC |
| CPRL | TRIP RELEASE CHARACTERISTIC | FIRST LOCATION INSTANTANEOUS |
| CPRL | TRIP RELEASE CHARACTERISTIC | SECOND LOCATION TIME DELAY |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 120.0 |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 1 |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | BETWEEN POLE ONE AND TWO |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | FIRST LOCATION SERIES TRIP |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SECOND LOCATION RELAY TRIP |
| CQJX | NOMINAL THREAD SIZE | INCHES 0.375 |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | SECOND LOCATION MINIMUM AT 200 PCT 0.100 AND MAXIMUM AT 200 PCT 0.700 |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | HERMETICALLY SEALED AND SHOCKPROOF AND VIBRATIONPROOF |
| CTJS | UNPACKAGED UNIT WEIGHT | OUNCES NOMINAL 3.600 |
| FREQ | FREQUENCY IN HERTZ | 60.0 |
| THSD | THREAD SERIES DESIGNATOR | UNEF |
| TTQY | TERMINAL TYPE AND QUANTITY | WIRE HOOK 5 |